The CBT3 and CBT4 are hand-held
instruments for testing residual current
protective devices (RCDs) in wiring
installations.
Poskytujeme kalibraci měřících přístrojů v naší akreditované kalibrační laboratoři elektrických veličin K 2356
Poptat kalibraciThe instruments are
connected through a normal mains
socket outlet or directly via the RCDs
terminals. Neons indicate if there are
no open circuits in the installation and
if the phase connections are correct.
A rotary switch selects the RCD rating
from one of six values available and a
membrane push-button is pressed to
execute a test. A known fixed current,
determined by the type of test select-
ed, flows to earth in the installation the
RCD is protecting, for a given length of
time. The types of test available are:-
(i) a ‘no trip’ test carried out at half
the rating selected, the result of
which should be that the device
under test does not trip.
(ii) a ‘trip’ test carried out at the rating
selected, the result of which
should be that the device trips
within the time specified for that
particular design of breaker
.
(iii) a test carried out at 150 mA and
designed for testing devices (up to
30 mA rating) fitted to protect
against direct contact with the
installation. The result should be
that the device trips within 40 ms.
(iv) a test carried out at five times the
rating selected, the result of which
should be that the device trips
within 40 ms